New rules for energy storage: higher thresholds, clear rules and further challenges to resolve
Higher energy storage capacity thresholds, the possibility of installing up to 600 kWh in a single fire zone and, for the first time, detailed rules for installing storage in multi-family buildings - these are the most important solutions in the draft regulation on energy storage, which the Polish Energy Storage Association (PSME) assesses positively. However, the organisation stresses that although the draft is the result of broad consultations involving the industry and is an important step towards greater safety and market development, some provisions still need refining so that the new rules are fully consistent with applicable standards and the realities of the technologies used.
- For the first time we have a comprehensive draft regulating the installation of energy storage in buildings. This is a very important step for the entire market. We are pleased that the draft takes into account both the safety of users and emergency services and the development of modern energy storage technologies. At the same time, we believe that during the consultations it will be possible to refine a few provisions so that the rules are unambiguous and workable in practice - says Barbara Adamska, President of the Polish Energy Storage Association (PSME).
The draft regulation introduces comprehensive requirements for battery energy storage systems (BESS) with a capacity exceeding 2 kWh. It sets out obligations concerning battery management systems (BMS), emergency switches, storage location, fire protection, ventilation, detection systems and requirements for installations in single-family and multi-family buildings.
A clear division of requirements depending on storage size
The draft differentiates requirements as the capacity of the energy storage system increases. This covers requirements for fire separation as well as detection systems, ventilation and fixed extinguishing equipment. This approach reflects the actual level of risk and avoids imposing the same obligations on small storage units used in single-family homes and on large commercial installations.
- The most important change is the move away from a uniform, very restrictive approach to all energy storage towards requirements tailored to the actual scale of the installation and the level of risk - stresses Dr hab. inż. Dariusz Zieliński, Professor at the Lublin University of Technology, member of the PSME Working Group on Safety.
- One of the most important outcomes of the consultations is raising the capacity thresholds above which more demanding fire protection measures apply. The final version of the draft clearly distinguishes four capacity classes: up to 30 kWh, 30-60 kWh, 60-120 kWh and above 120 kWh. As a result, many storage systems that under the original assumptions would have been subject to requirements intended for industrial installations can be designed with much simpler technical requirements - the expert adds.
As PSME experts point out, the change most noticeable for the market is the shift of capacity thresholds from 10/50/100 kWh to 30/60/120 kWh. This means that a significant proportion of energy storage systems used in residential and service buildings and small industrial plants can be designed with less stringent technical and fire requirements than the original draft envisaged.
For storage up to 30 kWh, typical of home installations, only basic requirements remain: autonomous smoke and carbon monoxide detectors and relatively small fire separation. Further requirements concerning the fire resistance of rooms, fire alarm systems and extinguishing equipment are introduced gradually only as capacity increases.
- This approach means abandoning the principle of "one level of requirements for all" and better reflects the actual risk associated with operating storage systems of different sizes - concludes Dr inż. Marcin Koniak of the Warsaw University of Technology, member of the PSME Working Group on Safety.
Positive assessment of the 600 kWh limit per fire zone
One of the most important provisions of the draft is the possibility of installing up to 600 kWh of energy storage in a single fire zone of a building not intended exclusively for energy storage. In the view of PSME experts, this is a rational solution that meets market needs and allows larger installations to be designed without excessively dividing buildings into additional fire zones.
At the same time, the organisation stresses that creating fire zones still requires meeting stringent requirements for the fire resistance of partitions, the sealing of service penetrations and the use of appropriate fire doors.
- The 600 kWh limit per fire zone is an example of a solution showing that dialogue between the administration, the State Fire Service and the industry delivers tangible results. The Polish Energy Storage Association took an active part in the entire consultation process for the draft regulation, submitting comments and presenting arguments based on market experience and international practice. We are pleased to see that many of these proposals have been taken into account - says the President of the Polish Energy Storage Association (PSME).
Energy storage in multi-family buildings
For the first time, the draft sets out detailed rules for installing energy storage in flats in multi-family buildings. It permits storage with a capacity of up to 11 kWh and a charging and discharging power of up to 3.7 kW, while setting requirements for location, labelling, smoke and carbon monoxide detectors and the use of fire-resistant cabinets or separate technical rooms.
In the view of PSME experts, the 11 kWh capacity limit meets the needs of most individual users. However, the justification for limiting power to 3.7 kW raises doubts.
- From a fire safety point of view, the key parameter is the capacity of the energy storage system, not its power. At the same time, we understand that the power limit may result from the need to ensure stable operation of the power grid, especially in multi-family buildings. However, the explanatory memorandum should clearly distinguish between requirements arising from fire safety and those related to the functioning of the power system - stresses Barbara Adamska.
Location of energy storage outdoors
Another important outcome of the public consultations was the refinement of the rules for locating energy storage installed outside buildings. In the original draft the requirements were more general and were based mainly on maintaining minimum distances from buildings and basic location restrictions. The final version abandons this approach in favour of detailed design rules. It explicitly permits storage to be located less than 4 m from a building, on the facade and on a flat roof, while setting out the conditions for safe installation.
Limits were introduced of 120 kWh for storage installed against a building wall or less than 4 m from it, and 600 kWh for storage installed on flat roofs. The draft also sets the maximum capacity of individual battery groups (30 kWh on a facade and 120 kWh on a roof), minimum distances between groups (1.5 m horizontally and 3 m vertically), required distances from windows, doors, ventilation openings, eaves, roof hatches and smoke vents, as well as requirements for the non-combustibility of facades and roof coverings. As a result, designers have received much more complete and unambiguous guidelines for safely designing outdoor storage next to existing buildings.
The specific nature of safer technologies has been recognised
A very important outcome of the consultations is that separate rules have been kept for technologies that do not show the thermal runaway hazards characteristic of lithium-ion batteries.
- Batteries with an aqueous electrolyte (e.g. lead-acid batteries) and increasingly popular flow batteries have been exempted from some of the most restrictive obligations, including requirements for battery management systems (BMS), location restrictions, gas detection requirements and some fire protection obligations - stresses Dr inż. Krzysztof Rafał of the Polish Academy of Sciences Research Centre "Energy Conversion and Renewable Sources", member of the PSME Working Group on Safety.
This is the first time Polish regulations have so clearly differentiated requirements according to the energy storage technology, and it confirms that the level of protection should correspond to the actual level of hazard.
Some areas still need refining
Despite significant changes, the draft still contains solutions that require further legislative work.
This applies above all to the very restrictive thresholds for voltages remaining live after the emergency switch has operated, and the lack of clear rules for designing flammable gas detection and ventilation systems for lithium-ion storage.
Following an analysis of the draft regulation, PSME experts recommend changing the thresholds for the voltage remaining after the emergency switch has operated. The organisation proposes adopting values of 25 V AC and 60 V DC instead of the proposed 12 V AC and 30 V DC. Under Polish standards, the proposed values correspond to the safe voltage used in conditions of increased hazard.
In the experts' view, the proposed solution better reflects the technologies currently in use.
The standard in home energy storage is systems operating at 48 or 51.2 V DC, whose end-of-charge voltage is below 60 V DC. Adopting the higher thresholds will maintain a high level of safety for rescue teams while taking into account the technical parameters of the vast majority of energy storage systems currently on the market.
- Polish and European standards on protection against electric shock provide for different safe voltage values depending on environmental conditions and the level of shock hazard. For conditions of increased hazard, the values commonly adopted are 25 V AC and 60 V DC, while for normal conditions the standards permit higher values. The draft regulation adopts 12 V AC and 30 V DC, corresponding to the most restrictive approach, without giving a technical justification. At the same time, this provision forces the use of additional high-power switching devices to disconnect the battery circuit, interfering with the energy storage manufacturer's certified configuration and increasing the number of components that could be a potential source of failure or ignition - the President of the Polish Energy Storage Association (PSME) explains the experts' concerns.
In the view of PSME experts, the proposed change does not reduce the level of safety for people
operating the installation or for rescue teams. The proposed touch-safe voltage values have
been used for many years as safe for conditions of increased shock hazard and are a recognised compromise between safety and the functionality of electrical installations. Adopting these values maintains a high level of protection against electric shock while eliminating the need for additional disconnecting devices in typical low-voltage energy storage systems with an operating voltage of up to 60 V.
The direction of change is assessed positively
PSME stresses that the draft regulation is a long-awaited step towards putting the rules for designing and installing energy storage in Poland in order. Introducing uniform requirements will increase user safety, make the work of emergency services easier and give investors and manufacturers greater predictability.
- Energy storage is becoming one of the foundations of the energy transition. That is why we need regulations that are modern, safe and workable in practice. We see this draft as a very good basis for such regulations and hope that the final version of the regulation will be the result of dialogue between the administration, the fire service and the entire industry - concludes Barbara Adamska.
The Polish Energy Storage Association (PSME) is the leading organisation of the energy storage and battery industry in Poland. It brings together companies and other entities operating in the energy storage and battery sector: manufacturers, integrators, developers, investors, contractors, EPC companies, recycling companies and research and scientific institutions. It takes part in legislative work and in shaping non-legislative measures, carries out educational and information activities and promotes safety standards for the use of energy storage, taking into account legal, technical and economic security.